Installation and Maintenance Manual
22
Wiring Control Inputs to the Smart Touch Controller
1. Test the basic open and close operator function before wiring the external control inputs. This
makes it easier to troubleshoot if an unexpected function issue arises.
2. Each input has an LED to indicate when that input is active. To disclose the input status, the LED
tact button must be pushed. This button is in corner near the Stop input.
3. All the control device inputs listed below are shown as a single input because the other wire is
connected the Common Terminal Buss on the Power Supply board. The Emergency Close and
Fire Dept. Open inputs are an exception and require a +24 Volt input in order to be activated.
The +24 is available at the spade terminals next to the Common Buss.
Smart Touch Controller Inputs
1)
*
Stop Push button
(N.C. input, jumper to Common if unused)
2)
*
Open Push Button
(not for radio or remote access controls)
3)
*
Close Push button
(not for radio or remote access controls)
4) Remote Open & Radio Control
(For radio / remote open device -
menu opt. to also close)
5) Open/Close button
(pushbutton or radio controls)
6) Partial Open
(this input disabled on swing gates)
7) Open interlock input or Time clock Open
(menu configurable)
8) Free Exit vehicle detector
9) Disable Free Exit vehicle detector
10) Inside Obstruction vehicle detector
(Inside reversing loop)
11) Outside Obstruction vehicle detector
(Outside reversing loop)
12) Shadow vehicle detector
(This is the loop under the arc of the gate)
13) Edge Sensor
(one input works for both directions of travel)
(14-15) Photo eye Common Power
(supply for PE power & PE Com)
(17) Photo eye Open direction
(beam spans the area where gate
opens)
(19) Photo eye Close direction
(beam spans across the road)
(21) Charger AC power loss
(only used in battery type operators)
(22) Spare Input
(unused – may have function in custom applications)
(23)
*
Emergency Close
(must menu enable and input +24 Volts to
trigger) Overrides photo eyes, gate edge & vehicle detectors.
(24)
*
Fire Dept. Open
(must menu enable and input +24 Volts to trigger)
Overrides photo eyes & gate edge.
*
Do not connect an external control to terminals #1, 2 or 3,
unless the controls are located such that there is a clear view
of the entire gate area. For controls not within sight, use
input terminals #4, 5, 6 or 7.
*
The Emergency Close and Fire Dept. Open inputs are to be used only if
access to these controls are guarded in sufficient manner such that there
is always supervision when activated.
Attention
Содержание HRG 220 ST
Страница 15: ...Installation and Maintenance Manual 9 Swing Gate Post Details ...
Страница 16: ...Installation and Maintenance Manual 10 HRG 220 Pump Pack ...
Страница 17: ...Installation and Maintenance Manual 11 HRG 222 Pump Pack ...
Страница 18: ...Installation and Maintenance Manual 12 How Our Hydraulic Swing Gates Work ...
Страница 25: ...Installation and Maintenance Manual 19 Instructions for Hand Pump or Manual Operation ...
Страница 29: ...Installation and Maintenance Manual 23 ...
Страница 47: ...Installation and Maintenance Manual 41 ...
Страница 48: ...Installation and Maintenance Manual 42 ...
Страница 62: ...Installation and Maintenance Manual 56 Battery Connection Diagram ...
Страница 63: ...Installation and Maintenance Manual 57 Battery Connection Diagram ...
Страница 65: ...Installation and Maintenance Manual 59 Wire Size Schedules ...
Страница 66: ...Installation and Maintenance Manual 60 Parts Breakout HRG 220 Pump Packs ...
Страница 67: ...Installation and Maintenance Manual 61 Parts Breakout HRG 222 Pump Packs ...
Страница 68: ...Installation and Maintenance Manual 62 Parts Breakout Control Box ...
Страница 69: ...Installation and Maintenance Manual 63 Parts Breakout Post ...
Страница 70: ...Installation and Maintenance Manual 64 Parts Breakout DC Power Supply ...