Installation and Maintenance Manual
4
Install An Automatic Swing Gate Operator Only When:
Y
The gate moves freely in both directions. Never over-tighten a clutch or pressure relief
valve to compensate for a stiff moving gate.
Y
The operator will not swing the gate into a public access area.
Y
The operator will be properly electrically grounded and the intended supply voltage matches
the voltage label on the operator.
Y
The operator controls will be located in a clear line-of-sight to the gate. Radio controls and
other remote access controls must be connected only to the
Remote Open input.
Y
The required external entrapment sensors will be installed. Be certain to carefully review
the instructions for placement, installation and adjustment of these external entrapment
sensors. External entrapment sensors must function to reverse the movement of the gate
in both the opening and closing directions.
If edge (contact) sensors are used, they are
to be located on the inside and outside leading edge of the swing gate and along the bottom
edge of a swing gate that is greater than 6” above the ground. If photo eyes or other non-
contact sensors are used, they are to be mounted in locations most likely to guard against
entrapment. A combination of contact and non-contact sensors may be used, but all must
be recognized components under the UL 325 standard. See pages 32 and 33 for details on
the requirements.
Y
If the Entrapment protection is provided by a continuous pressure actuation control, a
placard must be installed next to the control station stating “WARNING” – “Moving Gate has
the Potential of Inflicting Injury or Death - Do Not Start Gate Unless Path is Clear.”
Additionally, no other activation device shall be connected and an automatic closing device
of any kind shall not be used.
Y
The automatic operator is labeled as appropriate for both the type and UL usage class of
the gate.
Class I: Intended to serve single to four family residential uses
Class II: Multi-family use, or any application intended to serve the general public
Class III: Commercial applications
not
intended to serve the general public
Class IV: Highest security. Security personnel prevent unauthorized access
Содержание HRG 220 ST
Страница 15: ...Installation and Maintenance Manual 9 Swing Gate Post Details ...
Страница 16: ...Installation and Maintenance Manual 10 HRG 220 Pump Pack ...
Страница 17: ...Installation and Maintenance Manual 11 HRG 222 Pump Pack ...
Страница 18: ...Installation and Maintenance Manual 12 How Our Hydraulic Swing Gates Work ...
Страница 25: ...Installation and Maintenance Manual 19 Instructions for Hand Pump or Manual Operation ...
Страница 29: ...Installation and Maintenance Manual 23 ...
Страница 47: ...Installation and Maintenance Manual 41 ...
Страница 48: ...Installation and Maintenance Manual 42 ...
Страница 62: ...Installation and Maintenance Manual 56 Battery Connection Diagram ...
Страница 63: ...Installation and Maintenance Manual 57 Battery Connection Diagram ...
Страница 65: ...Installation and Maintenance Manual 59 Wire Size Schedules ...
Страница 66: ...Installation and Maintenance Manual 60 Parts Breakout HRG 220 Pump Packs ...
Страница 67: ...Installation and Maintenance Manual 61 Parts Breakout HRG 222 Pump Packs ...
Страница 68: ...Installation and Maintenance Manual 62 Parts Breakout Control Box ...
Страница 69: ...Installation and Maintenance Manual 63 Parts Breakout Post ...
Страница 70: ...Installation and Maintenance Manual 64 Parts Breakout DC Power Supply ...