Installation and Maintenance Manual
26
Smart Touch Controller Installer Menu Functions
The Installer Menu can be accessed only by entering the User Menu first, and then by
pressing the
Reset button and the Open button
simultaneously.
To restore the factory default settings, go to menu item [Fd_0] and change the setting to 1, then press
the Program Menu button. The entire menu will reset to the factory defaults.
Installer Menu Options
Default
Description
I1
[uC 0] Set UL Usage Class
0
0 = Gate disabled, Set Class 1 through 4 use
I2
[Fd 0] Load Factory Defaults
0
0 = User settings, 1 = Load defaults (resets full menu)
I3
[dg 0] Set Master/Slave type
0
0 = Solo operator, 1 = Slave unit, 2 = Master unit
I4
[Ch 0] Set AC Charger or Solar
0
0 = DC + AC charger, 1 = DC + Solar charger
I5
[Fo 0] Enable Fire Dept. Open
0
0 = input disabled, 1 = enabled
I6
[oC 0] Enable Emergency close
0
0 = input disabled, 1 = enabled
I7
[SE 3] Inherent Sensor sens.
3
1 = Maximum sensitivity, 9 = Lowest sensitivity
I8
[SS 0]
Inherent Sensor function
0
1 = stop only (note, functions in usage class 4 only)
I9
[LC 0]
Leaf delay Close
0
0 = none (1-7) ½ second steps (Master/Slave only)
I10
[Lo 0]
Leaf delay Open
0
0 = none (1-7) ½ second steps (Master/Slave only)
I11
[rt 0] Maximum run timer
0
0 = 60 Seconds max run, 1 = 300 Seconds max run
I12
[EC 0] PEC reverse to open
0
0 = Close eye stops only, 1 = 2 sec reverse to open
I13
[EO 0] PEO reverse to close
0
0 = Open eye stops only, 1 = 2 sec reverse to close
I14
[gr 0] Edge reverse to open
0
0 = Edge reverses fully open, 1 = Edge reverses for 2 sec
I15
[Sr 1] IES reverse to open
1
0 = IES reverses fully open, 1 = IES reverses for 2 sec
I16
[PC 0] Set PEO/ PEC – NO/NC
0
0 = Normally Open PE output, 1 = N.C. (Supervised)
I17
[gC 0] Set Edge input – NO/NC
0
0 = Normally Open Edge output, 1 = Normally Closed
I18
[tC 1] Time clock/ Interlock input
1
0 = select Time Clock, 1 = select Open Interlock
I19
[or 1] OOLD detector function
1
0 = pause closing only, 1 = enable reversing to open
I20
[ir 1] IOLD detector function
1
0 = pause closing only, 1 = enable reversing to open
I21
[hd 1] SLD Shadow detector funct
1
0 = Hold open only, 1 = Hold Hold open
I22
[dL 1] Vehicle detector logic
1
1 = Std, 2 = Close timer counts down even with loops active
I23
[r1 0] User relay 1 option
1
0 = disabled, 1 – 19 = see relay output options page 31
I24
[r2 0] User relay 2 option
6
0 = disabled, 1 – 19 = see relay output options page 31
I25
[r3 0] User relay 3 option
1
0 = disabled, 1 – 19 = see relay output options page 31
I26
[tL 0]
Gate Open alert
2
0 = 0 sec, 1= 15s, 2= 45s, 3= 75s, 4= 105s, 5= 135s
I27
[Lt 0]
Loitering alert
3
0 = 0 sec, 1= 15s, 2= 45s, 3= 75s, 4= 105s, 5= 135s
I28
[ELd0] Test factory ELD*
0
0=Run, 1=show freq, 2=show call level 0-7, 3=set freq 1-4
I29
[iLd0] Test factory IOLD*
0
0=Run, 1=show freq, 2=show call level 0-7, 3=set freq 1-4
I30
[oLd0] Test factory OOLD*
0
0=Run, 1=show freq, 2=show call level 0-7, 3=set freq 1-4
I31
[SLd0] Test factory SLD*
0
0=Run, 1=show freq, 2=show call level 0-7, 3=set freq 1-4
*See page 46 for description of vehicle detector & Loop Fault diagnostics
These Notes Refer to the Menu Above:
I1
This setting must be configured or the gate cannot function and menu will not exit.
I4
This setting appear only if the factory has provided a DC powered gate operator
I8
IES stop only setting [SS __] does not appear unless set as a class 4 operator
I9-10
These settings appear only if the Installer Menu is set for Master / Slave function
I26-27
These settings appear only if the Installer Menu has set relays r1-r3 for these alerts
Содержание HRG 220 ST
Страница 15: ...Installation and Maintenance Manual 9 Swing Gate Post Details ...
Страница 16: ...Installation and Maintenance Manual 10 HRG 220 Pump Pack ...
Страница 17: ...Installation and Maintenance Manual 11 HRG 222 Pump Pack ...
Страница 18: ...Installation and Maintenance Manual 12 How Our Hydraulic Swing Gates Work ...
Страница 25: ...Installation and Maintenance Manual 19 Instructions for Hand Pump or Manual Operation ...
Страница 29: ...Installation and Maintenance Manual 23 ...
Страница 47: ...Installation and Maintenance Manual 41 ...
Страница 48: ...Installation and Maintenance Manual 42 ...
Страница 62: ...Installation and Maintenance Manual 56 Battery Connection Diagram ...
Страница 63: ...Installation and Maintenance Manual 57 Battery Connection Diagram ...
Страница 65: ...Installation and Maintenance Manual 59 Wire Size Schedules ...
Страница 66: ...Installation and Maintenance Manual 60 Parts Breakout HRG 220 Pump Packs ...
Страница 67: ...Installation and Maintenance Manual 61 Parts Breakout HRG 222 Pump Packs ...
Страница 68: ...Installation and Maintenance Manual 62 Parts Breakout Control Box ...
Страница 69: ...Installation and Maintenance Manual 63 Parts Breakout Post ...
Страница 70: ...Installation and Maintenance Manual 64 Parts Breakout DC Power Supply ...