Installation and Maintenance Manual
19
Wiring Control Inputs to the Smart Touch Controller
1. Test the basic open and close operator function before wiring the external control inputs. This makes it
easier to troubleshoot if an unexpected function issue arises.
2. Each input has an LED to indicate when that input is active. To disclose the input status, the LED tact
button must be pushed. This button is in corner near the Stop input.
3. All the control device inputs listed below are shown as a single input because the other wire is con-
nected the Common Terminal Buss on the Power Supply board. The Emergency Close and Fire Dept.
Open inputs are an exception and require a +24 Volt input in order to be activated. The +24 is avail-
able at the spade terminals next to the Common Buss.
Smart Touch Controller Inputs
1) *Stop Push button (N.C. input, jumper to Common if unused)
2) *Open Push Button (not for radio or remote access controls)
3) *Close Push button (not for radio or remote access controls)
4) Remote Open & Radio Control (For radio / remote open device -
menu opt. to also close)
5) Open/Close button (pushbutton or radio controls)
6) Partial Open (installer adjustable from 7- 99 seconds)
7) Open interlock input or Time clock Open (menu configurable)
8) Free Exit vehicle detector
9) Disable Free Exit vehicle detector
10) Inside Obstruction vehicle detector (Inside reversing loop)
11) Outside Obstruction vehicle detector (Outside reversing loop)
12) Shadow/Reset vehicle detector (Shadow is for Swing gates only)
(Reset function is for Arm gates)
13) Edge Sensor (one input works for both directions of travel)
(14-15) Photo eye Common Power (supply for PE power & PE Com)
(17) Photo eye Open direction (spans the gate storage area)
(19) Photo eye Close direction (spans the roadway)
(21) Charger AC power loss (only used in battery type operators)
(22) Spare Input (unused - may have function in custom applications)
(23) *Emergency Close (must menu enable and input +24 Volts to
trigger) Overrides photo eyes, gate edge & vehicle detectors.
(24) *Fire Dept. Open (must menu enable and input +24 Volts to
trigger) Overrides photo eyes & gate edge.
* Do not connect an external control to terminals #1, 2 or 3,
unless the controls are located such that there is a clear
view of the entire gate area. For controls not within sight,
use input terminals #4, 5, 6 or 7.
*The Emergency Close and Fire Dept. Open inputs are to be used only
if access to these controls are guarded in sufficient manner such that
there is always supervision when activated.