WARNING

• Turn OFF all power to the Automatic Door if a Safety System is not working.

• Instruct the Owner to keep all power turned OFF until corrective action can be achieved by a NABCO 

trained technician. Failure to follow these practices may result in serious consequences.

• NEVER leave a Door operating without all Safety detection systems operational.

Swing Door Operator 

Wiring and Adjustment Manual 

** with Magnum 4A Control*

DN 0557

LED

TRANSFORMER

AUX

PWR

J2

J5

AC IN

SW2

SW1

F1

RELAY

RELAY

J4

TDAS

SIGNAL

INPUT

TDPG

LCHK

CLOSE

Fuse 1: 0.5A 24 VAC

STOP

OPEN

BCHK

CURRENT

LIMIT

MOTOR

J1

R28

MAGNUM 4A

F2

Fuse 2: 5A 120/240

Capacitor

MOV

12

34

O

F

F

Содержание Magnum 4A Control

Страница 1: ...rrective action can be achieved by a NABCO trained technician Failure to follow these practices may result in serious consequences NEVER leave a Door operating without all Safety detection systems ope...

Страница 2: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 3: ...rness 3 8 Section 3b Power Harness 3 9 Section 3c Motor Harness 300 400 500 3 10 Section 3d Motor Harness 710 8310 8710 3 10 Section 3e Fuses 3 10 CHAPTER 4 ADJUSTMENTS AND STATUS LEDs 4 11 Section 4a...

Страница 4: ...8710 Simultaneous Pair w One Magnum 4A Control 7 26 Section 7g GT 1400 Single Fold with One Magnum 4A Control 7 27 Section 7h GT 1400 Bi Fold with Two Magnum 4A Controls 7 28 Section 7i GT 1400 Bi Fol...

Страница 5: ...ability of severe injury or death It should not be considered for property damage unless personal injury risk is present Indicates a hazardous situation which has some probability of severe injury It...

Страница 6: ...ed qualified electrical technicians and comply with all applicable governing agency codes Do not place finger or uninsulated tools inside the electrical controller Touching wires or other parts inside...

Страница 7: ...w Energy swing doors Other local standards or codes may apply Use them in addition to the ANSI standards Instruct the building owners and operator on the essentials of the operation of the Magnum 4A C...

Страница 8: ...Current Limit potentiometer 2 Position Slide Switch to permit the installer to choose Low Energy or Full Automatic mode of operation Section 2a Electrical Specifications All Wiring Diagrams included w...

Страница 9: ...4A Control must not exceed 500mA 0 5 amps when outputting power to Sensors Modules Accessories Auxiliary Equipment If TOTAL current draw exceeds 500 mA 0 5 amps the installer must utilize an auxiliary...

Страница 10: ...able Fuse N A F2 Not Rese ableFuse N A LED TRANSFORMER AUX PWR J2 O F F 12 4 3 J5 AC IN SW2 SW1 F1 RELAY RELAY J4 TDAS SIGNAL INPUT TDPG LCHK CLOSE Fuse 1 0 5A 24 VAC STOP OPEN BCHK CURRENT LIMIT MOT...

Страница 11: ...ted Presence Sensors or Mats on pull side of door X X When Pin 4 is shorted to Pin 5 Sensor or Mat will Prevent door from opening if already closed Hold door open if already open X X Circuit is only a...

Страница 12: ...le Outputs power from J5 Motor Feed Terminal to Motor Leads Slows door down if Brake Module Connector is accidently unplugged from J5 Section 3d Motor Harness 710 8310 8710 Figure 5 Motor Harness 710...

Страница 13: ...from fully closed Latch Check 10 from fully closed to fully closed Section 4b Adjustments Adjustments to the Magnum 4A Control can be made using the Dip Switch SW1 or the the Potentiometer 1 8 or the...

Страница 14: ...o is only active when door is pushed out of latch check X X Door opens when pushed Switch 4 must be turned On for door to time out and close 4 On Timer Mode X X Door will open time out and then close...

Страница 15: ...er is reduced from back check power to Stop power assuming stop power is lower than back check power This reduces the risk of the motor overheating at hold open allowing the door to close as well as r...

Страница 16: ...omatic door 1 60 seconds Low Energy door Event Action Hold Open time requires adjustment X X Recommended start position 12 o clock X X Dip Switch 4 must be ON X X Clockwise Increases time door will st...

Страница 17: ...unterclockwise Decreases closing speed Note The GT 710 uses the LCN Closer to regulate closing and latch check speed Current Limit Adjusts how hard the door will push against an obstacle while opening...

Страница 18: ...4 3 Status LED Indicators LED Status Description Green Cycle Indicates door position during an open and closed cycle Indicator Action Fast Flashing 2 flashes per second Door is opening On Solid Door...

Страница 19: ...Access Hole located at the left or right side of Header End Cap a It is recommended for the Installer to house all Incoming 120 VAC wires within an Electrical Conduit Keep all Incoming 120 VAC wiring...

Страница 20: ...when the door is broken out When door is broken out the Panic Breakout Switch CLOSES the circuit to activate the Continuous Safety feature and disable the Operator 1 Turn OFF Power 2 Go to Panic Latc...

Страница 21: ...E Fuse 1 0 5 A 24 VAC STOP OPEN BCHK CURRENT LIMIT MOTO J1 R28 MAGNUM 4A R Fuse 2 5 A120 240 Capacitor MOV 11 Go to ends of each Red wire connected to Panic Latch Harness Cut white plastic connectors...

Страница 22: ...y with Lockout during door swing To Terminal 5 Normally Closed Contacts Continuous Safety Normally Closed Contacts Red Red Part 11 0941 Panic Latch Kit TERMINAL BLOCK 1 BROWN 2 ORANGE 3 VIOLET 4 WHITE...

Страница 23: ...ivation Signals to Terminals 5 and 6 Directly Part 10 3528 RS 12 Rocker Switch Red Red Part 11 0941 Panic Latch Kit When the unit has Panic Breakout feature Breakout Limit Switch Signal and or Panic L...

Страница 24: ...TY OUTPUT FROM DOOR MOUNTED SWING SIDE SENSOR Arrow marked EXT points into the building Contacts must close when door is broken out If door can break out black and brown wires from the operator should...

Страница 25: ...MOUNTED SWING SIDE SENSOR O F F 12 4 3 AUX PWR J2 J5 AC IN F2 SW2 SW1 F1 R2 R3 R4 R5 R6 R7 R8 TDAS TDPG LCHK CLOSE STOP OPEN BCHK CURRENT LIMIT MOTOR J1 R28 MAGNUM 4A LED TRANSFORMER RELAY RELAY J4 S...

Страница 26: ...VAC HOT 120 VAC NEUTRAL SERVICE GROUND MINIMUM 5 AMPERE SERVICE PER OPERATOR BLACK GROUND RED WHITE BLACK TO TERMINAL 5 TO TERMINAL 5 GREEN RED BLACK FOR RIGHT HAND OPERATORS MATCH MOTOR WIRES RED TO...

Страница 27: ...ART 22 10065 MAIN HARNESS BLACK BLACK BLACK GREEN WHITE 120 VAC HOT 120 VAC NEUTRAL SERVICE GROUND MINIMUM 5 AMPERE SERVICE PER OPERATOR BLACK GROUND RED WHITE BLACK TO TERMINAL 5 TO TERMINAL 5 GREEN...

Страница 28: ...AMPERE SERVICE PER OPERATOR 120 VAC NEUTRAL 120 VAC HOT BLACK BLACK BLACK O F F 12 4 3 AUX PWR J2 J5 AC IN F2 SW2 SW1 F1 R2 R3 R4 R5 R6 R7 R8 TDAS TDPG LCHK CLOSE STOP OPEN BCHK CURRENT LIMIT MOTOR J1...

Страница 29: ...RT 22 10065 MAIN HARNESS 14 14362 BLACK BLACK BLACK BLACK BLACK BLACK WHITE GREEN GREEN WHITE WHITE 120 VAC HOT 120 VAC NEUTRAL SERVICE GROUND MINIMUM 5 AMPERE SERVICE PER OPERATOR NOTES 1 WIRES AT SE...

Страница 30: ...WHITE GREEN BLACK WHITE BLACK WHITE N C BREAK OUT SWITCHES RED VIOLET ORANGE BROWN MAIN HARNESS SIM PAIR PART 22 10270 TRANSFORMER 14 2101 120 VAC BROWN BLUE WHITE RED FOLD SIDE ACUVISION 14 10823 01...

Страница 31: ...ART 22 13952 Y HARNESS PART 22 10065 MAIN HARNESS 14 14362 BLACK BLACK BLACK BLACK BLACK BLACK BLACK WHITE GREEN GREEN WHITE 120 VAC HOT 120 VAC NEUTRAL SERVICE GROUND MINIMUM 5 AMPERE SERVICE PER OPE...

Страница 32: ...3 Spacer 240010 01 Brown Hot Blue Neutral Screw 218754 Transformer Transformer J4 Motor Black Green Ground Screw Cup Washer Black Black White Green wires are 24 volt AC and can be used to power access...

Страница 33: ...such as sensors from Terminals 1 and 2 and install an alternate power supply such as a Transformer Motor may be blown Replace motor Safety circuit is activated X X Check to ensure Dip Switch 2 is set...

Страница 34: ...Remove motor and operator from Header 2 Separate motor from operator 3 Inspect couplings for looseness Back Check adjustment on Magnum 4A has no effect Door is not going into Back Check at 80 position...

Страница 35: ...Terminal Block was to Continuous Safety not Safety w Lockout 1 Rewire Safety Sensor to Safety w Lockout 2 Go to Terminal Block 3 Connect the output of the Sensor to Terminal 5 Red Wire and Terminal 4...

Отзывы: