Table 3-10 Technical specifications of normal-temperature outdoor units
Item
NetCol500-A018
(Normal-
Temperature
Outdoor Unit)
NetCol500-A021
(Low-
Temperature
Outdoor Unit)
NetCol500-A020
(High-
Temperature
Outdoor Unit)
Power system
208–240 V AC,
50/60 Hz, 1 PH+N
+PE
220–240 V AC,
50/60 Hz, 1 PH+N
+PE
220–240 V AC,
50/60 Hz, 1 PH+N
+PE
Maximum
operating current
24A
30A
30A
Number of fans
One
1
2
Dimensions (H x
W x D)
966mm×1057mm
×339mm
1350mm×1270m
m×730mm
1327mm×966mm
×320mm
Package
dimensions (H x
W x D)
1210mm×1105m
m×435mm
1530mm×1355m
m×777mm
1485mm×1082m
m×435mm
Net weight/Gross
weight
83kg/99kg
196kg/229kg
101kg/114kg
Certification
REACH, RoHS, CE,
CCC, and CQC
REACH, RoHS, CE,
CCC, CQC, and
EAC
REACH, RoHS, CE,
and SASO
Environment type
Class B
Class B
Class B
Protection level
IPX4
IPX4
IPX4
Outdoor unit application environments are classified by severity as follows:
●
Class A (controlled environment): indoor environments where the ambient
temperature and humidity are controlled, including rooms where people live
●
Class B (uncontrollable environment): indoor environments where the
ambient temperature and humidity are not controlled or general outdoor
environments with simple shielding measures where the humidity reaches
100% occasionally
●
Class C (harsh environment): sea environments, or outdoor land environments
or environments with simple shielding measures, which are within 3.7 km
away from the sea or within 1.2 km away from a pollution source
●
Class D (marine environment): environments within 500 m away from the
coast
FusionModule800 Smart Small Data Center
User Manual
3 System Architecture
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
37