Parameter
Smart Cooling Product No.
1
2
3
4
Rotation time The
parameter
can be set by
the hour
ranging from
midnight to
23:00 as
required.
-
-
-
Requirement
control
Competitive
running
avoidance
-
-
-
Step 4 After setting teamwork control parameters, choose Monitoring > Cooling >
NetCol5000-A1 > Running Info > Teamwork Information and check that the
displayed teamwork control information is consistent with the parameter settings.
NO TICE
If the information displayed under Teamwork Information is inconsistent with
the parameter settings, check the teamwork control cable connection and
teamwork control parameter settings.
----End
5.2.2.3 Setting the Maximum Outdoor Fan Speed
If the equipment room is near a noise-sensitive place, such as an office or a
meeting room, limit the rotational speed of the indoor fan within 80% to lower
the noise.
Procedure
Step 1 Choose Monitoring > Cooling > NetCol5000-A1 > Running Parameters > Indoor
Fan Parameters, set Max speed of indoor fan to 80%.
Step 2 Set Max speed of indoor fan to 80% of other smart cooling products in turn.
----End
5.2.3 Commissioning the Cooling System
Prerequisites
Check that the indoor and outdoor units have been powered on.
FusionModule800 Smart Small Data Center
User Manual
5 Power-On Commissioning
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
262