UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
50
Port
Descript
ion
Connection
Method
Bolt
Specificat
ions
Bolt Hole
Diameter
Bolt Length Torque
PE
Crimped OT
terminals
M10
10.5 mm
30 mm
26 N•m
Table 3-5
Power cable terminal requirements for the UPS5000-E-200K-FM
Port
Descriptio
n
Connection
Method
Bolt
Specificat
ions
Bolt Hole
Diameter
Bolt Length Torque
Mains input Crimped OT
terminals
M10
10.5 mm
40 mm
26 N•m
Bypass
input
Crimped OT
terminals
M10
10.5 mm
40 mm
26 N•m
Battery
input
Crimped OT
terminals
M12
13.5 mm
60 mm
46 N•m
Output
Crimped OT
terminals
M10
10.5 mm
40 mm
26 N•m
PE
Crimped OT
terminals
M10
10.5 mm
30 mm
26 N•m
lists the requirements for power cable terminals of the UPS5000-E-300K-SM/SMT.
Table 3-6
Power cable terminal requirements for the 300 kVA cabinet
Port
Descript
ion
Recommende
d Connection
Method
Bolt
Specificat
ions
Bolt Hole
Diameter
Bolt Length Torque
Mains
input
Crimped OT
terminals
M12
13.5 mm
45 mm
46 N•m
Bypass
input
Crimped OT
terminals
M12
13.5 mm
45 mm
46 N•m
Battery
input
Crimped OT
terminals
M12
13.5 mm
45 mm
46 N•m
Output
Crimped OT
terminals
M12
13.5 mm
45 mm
46 N•m
PE
Crimped OT
terminals
M12
13.5 mm
30 mm
46 N•m
lists the recommended upstream input switch configurations for the UPS5000-E.