3 Installation
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
82
Figure 3-42
Bottom cabling
Single mains
For single mains, the copper bars between the mains and bypass input terminals do not
need to be removed, and bypass input cables do not need to be connected.
Step 5
Route the signal cables on the left sideof subracks along the left side of the cabinet and the
cables on the right side of subracks along the right side of the cabinet, and then bind the
cables to the cabinet, as shown in