UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
3 Installation
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
48
Table 3-3
Recommended cross-sectional areas for power cables
Item
UPS5000-E-200K-SM/FM
UPS5000-E-300K-SM/S
MT
50 kVA
100 kVA 150 kVA 200 kVA 250 kVA
300 kVA
Mai
ns
inpu
t
Mains input current
(A)
89
178
267
355
444
533
Recommen
ded
cross-sectio
nal area
(mm
2
)
L1
4 x 25
4 x 70
2 x (4 x
70)
2 x (4 x
95)
2 x (4 x
120)
2 x (4 x
150)
L2
L3
N
PE
25
35
70
95
120
150
Byp
ass
inpu
t
Bypass input current
(A)
76
152
228
304
380
456
Recommen
ded
cross-sectio
nal area
(mm
2
)
L1
4 x 25
4 x 70
2 x (4 x
70)
2 x (4 x
95)
2 x (4 x
120)
2 x (4 x
150)
L2
L3
N
PE
25
35
70
95
120
150
Out
put
Output current (A)
76
152
228
304
380
456
Recommen
ded
cross-sectio
nal area
(mm
2
)
U
4 x 25
4 x 70
2 x (4 x
70)
2 x (4 x
95)
2 x (4 x
120)
2 x (4 x
150)
V
W
N
PE
25
35
70
95
120
150
Batt
ery
inpu
t
Battery nominal
discharge current (A)
110
219
329
439
548
658
Battery maximum
discharge current (A)
131
263
394
525
657
788
Recommen
ded
cross-sectio
nal area
(mm
2
)
+
3 x 35
3 x 95
2 x (3 x
95)
2 x (3 x
120)
2 x (3 x
150)
2 x (3 x
185)
N
-
PE
35
50
95
120
150
185