UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
C Alarm List
Issue 02 (2017-02-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
280
Alarm
ID
(Alarm
ID-Caus
e ID)
Alarm
Name
Severit
y
Cause
Solution
protection
voltage is
greater
than the
upper
threshold.
The
configure
d number
of
batteries
is less
than the
actual
number.
The actual
number of
batteries
does not
meet
requireme
nts.
number of batteries matches the
actual number.
3.
Check that the actual number of
batteries meets requirements.
0036-2
Battery
maintenanc
e reminder
Warning
The time for
maintenance
arrives.
Maintain the batteries.
0037-1
Battery
undervoltag
e
Critical
The UPS
has
worked in
battery
mode for
an
extended
amount of
time.
The
charger is
faulty.
1.
Check whether the battery
voltage is normal.
2.
Check whether the output is
overloaded.
3.
Check whether any battery is
damaged. If yes, replace the
battery.
4.
Check whether any battery
charger generates an alarm. If
yes, replace the faulty module.
0040-7
Rectifier
abnormal
Critical
The fan
for the
power
module is
not
functionin
g
properly.
The air
channel
1.
Check that the air channel for
the module is free from
blockage.
2.
Check whether the fans are
functioning properly. Replace
the power module if the fans are
faulty.