4 User Interface
Issue 07 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
161
Figure 4-88
Setting the MDU IP address and SSL encrypted transmission mode on the RCCMD
client
Step 2
On the MDU WebUI, choose
Config.
>
RCCMD
, and set
RCCMD function
to
Enable
.
Step 3
On the WebUI of the MDU, the SSL encryption is set to
Enable
by default and does not need
to be set. If the RCCMD client is set to the unencrypted mode, you need to set the SSL
encryption to
Disable
on the server WebUI.
Step 4
Configure events. If you set the job type to
RCCMD Message
under
Inverter on
, specify the
IP address and port of the RCCMD client. The port is 6003 by default. If you need to modify
the port, modify the port on the RCCMD client at the same time to keep them the same. Enter
the message to be sent and set the message sending mechanism. For example, set it to
Immediately, once
.
Step 5
On the
Monitoring
>
Control
page, start the UPS, and the inverter mode will be triggered.
Send the message to the RCCMD client, indicating that the inverter is on.
Step 6
On the RCCMD client, you can view messages through the
View Event Log
at the upper left
corner.
----End