UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
5 Operations
Issue 07 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
190
Ensure that the load power is stable. When the system load power fluctuation is greater
than the rated capacity of half a module (for example, the single-phase load fluctuation is
greater than 4.17 kVA for a 25 kVA module), the UPS may enter and exit from hibernation
mode repeatedly.
Check that the number of redundant power modules and racks are appropriate. If the
number is insufficient, the UPS may not enter hibernation mode.
5.12.1 LCD
Procedure
Step 1
On the main screen, tap
System Info
and
. The
Settings
screen is displayed.
If you have not logged in, enter a user name and password, and tap
on the login screen
displayed.
Step 2
Tap
Advanced Param
. Tap
or
to browse the parameters, as shown in
Figure 5-31
Hibernation parameters on the LCD
Step 3
On the LCD, choose
Enable
from the
Paral. sys. hibernate
drop-down list box. A
confirmation message is displayed, as shown in