User Manual
3 Installation
Issue 07 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
50
When the primary loads are non-linear loads, increase the cross-sectional areas of the neutral wires
1.5–1.7 times.
When the mains input and bypass input share a power source, configure input power cables as mains
input power cables. In addition, cables listed in
apply only to the following conditions:
Cable routing mode: For the UPS5000-E-(25 kVA-75 kVA), the cables are installed along the wall or
on the floor (IEC-60364-5-52 C standards).
The ambient temperature is 30°C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%. The recommended
cable diameters in
meet the basic through-current requirements. Users should evaluate the
line voltage loss based on the actual cable length. If the voltage loss exceeds the requirements,
increase the cable diameter properly.
The cables are single- or multi-core 90°C soft power cables with a copper conductor.
lists the requirements for power cable terminals of the UPS and
battery cabinet.
Table 3-5
Power cable connector requirements for the UPS
Port
Description
Connection Method Bolt
Specifications
Bolt Hole
Diameter
Torque
Input
Crimped OT terminals
M10
11 mm
26 N·m
Battery input
Crimped OT terminals
M12
13 mm
46 N·m
Output
Crimped OT terminals
M10
11 mm
26 N·m
PE
Crimped OT terminals
M8
9 mm
13 N·m
Table 3-6
Power cable connector requirements for the battery cabinet
Port
Description
Connection
Method
Bolt
Specifications
Bolt Hole
Diameter
Torque
Battery input
Crimped OT
terminals
M12
13 mm
46 N m
PE
Crimped OT
terminals
M8
9 mm
13 N m
M10
11 mm
26 N m
lists the recommended upstream input switch configurations for the UPS.
Table 3-7
Upstream input switch configurations
Upstream Input
Switch
UPS5000-E-75K-BF
25 kVA
50 kVA
75 kVA
Input
63 A/3P
100 A/3P
160 A/3P