UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
5 Operations
Issue 07 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
184
5.6.4.2 Download over the WebUI
Procedure
Step 1
Log in to the WebUI.
Step 2
Choose
Query
>
Logs
, select logs from the
Log
drop-down list box, then click
Export
to
export logs.
Figure 5-23
Logs
----End
5.7 Transferring to Maintenance Bypass Mode
Context
You are advised to install a lock on the maintenance bypass switch. The lock core has a
diameter of 5–10 mm.
Strictly observe the following procedure to transfer the UPS to maintenance bypass mode.
Otherwise, loads may power off.
In maintenance bypass mode, the mains supplies power to the loads directly over the
maintenance bypass. If the mains is abnormal, the loads may power off.
Procedure
Step 1
Transfer the UPS to bypass mode.
Step 2
Close the maintenance bypass switch.
If the maintenance bypass switch is locked, unlock it first.
maintenance bypass switch. Turn on the switch to transfer the UPS to maintenance bypass
mode.