UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
3 Installation
Issue 07 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
46
Do not install the UPS in environments with conductive metal scraps in the air.
The optimal operating temperatures for valve-regulated lead-acid batteries (VRLA
batteries) are 20–30°C. Operating temperatures higher than 30°C shorten the battery
lifespan and operating temperatures lower than 20°C reduce the battery backup time.
3.1.1.3 Installation Clearances
Reserve sufficient clearances around the cabinet to facilitate operations and ventilation:
Reserve a clearance of at least 1000 mm from the front of the cabinet.
Reserve a clearance of at least 500 mm from the top of the cabinet.
When a top outlet kit is installed (no antiseismic kit is installed), you can install the
cabinet against a wall. When no top outlet kit is added, keep a clearance of at least 200
mm from the rear of the cabinet. If you need to perform operations at the rear of the
cabinet, keep a clearance of at least 500 mm.
Figure 3-2
Reserved clearances (unit: mm)
3.1.2 Tools and Instruments
Insulate installation tools to prevent electric shocks.
Prepare the following tools and meters indicated in