UPS5000-E-(25 kVA-75 kVA)-BF
User Manual
4 User Interface
Issue 07 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
131
If the BP/SYSMT switch is set to
Enable
, this parameter is displayed on the screen. A
user can set this parameter to determine whether the port is used to detect the status of
the PDU bypass input switch or system maintenance switch.
SPD/SYSOUT Switch
If the SPD/SYSOUT switch is set to
Enable
, the port has dry contact signal access. How
a user uses the port depends on the status of the SPD/SYSOUT switch.
SPD/SYSOUT switch function
If the SPD/SYSOUT switch is set to
Enable
, this parameter is displayed on the screen. A
user can set this parameter to determine whether the port is used to detect the status of
the PDU input surge protector or system output switch.
MUS05A DO_1 Action
Control the status of the DO_1 dry contact on the MUS05A dry contact card.
MUS05A DO_2 Action
Control the status of the DO_2 dry contact on the MUS05A dry contact card.
MUS05A DO_3 Action
Control the status of the DO_3 dry contact on the MUS05A dry contact card.
MUS05A DO_4 Action
Control the status of the DO_4 dry contact on the MUS05A dry contact card.
MUS05A DO_1
Corresponds to signal of the output dry contact DO_1 on the MUS05A.
MUS05A DO_2
Corresponds to signal of the output dry contact DO_2 on the MUS05A.
MUS05A DO_3
Corresponds to signal of the output dry contact DO_3 on the MUS05A.
MUS05A DO_4
Corresponds to signal of the output dry contact DO_4 on the MUS05A.
4.1.2.5 Maintenance Screen
On the
System Info
screen, tap
to display the
Maintenance
screen, as shown in
. If a user is not currently logged in, a dialog box will display for
entering a user name and password. The
Maintenance
screen provides buttons such as
Battery Maint.
,
USB Operations
,
Inv. ON
, and
Inv. OFF
.