UPS2000-G-3 kVA
User Manual (CTC)
A Alarm Handling
Issue 02 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
82
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
is in battery self-check
state.
Reduce the load or
replace the UPS with a
larger-capacity UPS.
0340-01
Maint.
breaker
ON
Minor
Automatic
clear
The UPS transfers to bypass
mode.
Possible cause: The
maintenance circuit breaker
is ON during UPS
maintenance.
Measure: Switch off the
maintenance circuit breaker
after maintenance.
61440-01
Flash
fault
Critical
Automatic
clear
Files may be damaged.
Possible cause: The flash
memory cannot be properly
read or written.
Measure: Contact Huawei
technical support for repair.