A Alarm Handling
Issue 02 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
73
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
Measure: Contact the
manufacturer to load
software.
0044-06
Incompa
tible ver.
Critical
Manual
clear/Power
-off clear
The UPS startup is not
allowed.
Possible cause: Software
and hardware versions do
not match.
Measure: Contact the
manufacturer to load
software.
0045-03
Charger
alarm
Critical
Manual
clear/Power
-off clear
The charger in the UPS
stops.
Possible cause: The charger
capacitor is faulty.
Measure: Contact Huawei
technical support for repair.
0045-04
Critical
Possible cause: The charger
output is short-circuited.
Measure: Rectify battery
port short circuits. After
you clear the alarm, restart
the UPS. If the alarm
persists, contact Huawei
technical support for repair.
0045-06
Critical
Automatic
clear
Possible cause: The
rectifier R4850G2 is faulty.
Measure: Contact Huawei
technical support for repair.
0045-07
Critical
Manual
clear/Power
-off clear
The charger in the UPS
stops.
(The 20 kVA has no action.)
Possible cause: The charger
is faulty.
Measure: Contact Huawei
technical support for repair.
0045-08
Critical
Manual
clear/Power
-off
clear/Auto
matic clear
The charger in the UPS
stops.
0045-09
Critical
Manual
clear/Power
-off clear
0045-10
Critical
0060-01
Inverter
fault
Critical
Power-off
clear
The inverter shuts down. The
UPS transfers to bypass
mode or has no output based
on the transfer logic.
Possible cause: The
inverter is faulty.
Measure: Contact Huawei
technical support for repair.