UPS2000-G-3 kVA
User Manual (CTC)
4 Control Panel
Issue 02 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
37
Communication Card Screen
1.
If an SNMP card is connected, set the following parameters:
Figure 4-18
SNMP card settings
−
IP alloc.
parameter
Specifies the DHCP address allocating mode. The options include
Manual
and
Automatic
. The default value is
Manual
. After the allocating mode is set to
Automatic
, an
Allocating
dialog box is displayed on the screen. If allocation
succeeds, the new IP address is displayed. If allocation fails, the IP address restores
to the default one: 192.168.0.10. If the allocating mode is set to
Automati
c, you can
only query the IP address but cannot set the IP address manually.
If the UPS monitor does not support the DHCP function, after the DHCP is selected for the SNMP card,
you cannot set the IP address of the SNMP card on the UPS monitor. You are advised to update the
version of the UPS monitor.
−
IP address
parameter
Set an IP address for the SNMP card. The value ranges from
1.0.0.0
to
223.255.255.255
. The default value is
192.168.0.10
.
−
Subn. mask
parameter
Set a subnet mask for the SNMP card. The value ranges from
0.0.0.0
to
255.255.255.255
. The default value is
255.255.255.0
.
−
Gateway
parameter
Set a gateway address for the SNMP card. The value ranges from
1.0.0.0
to
223.255.255.255
. The default value is
192.168.0.1
.
2.
If a Modbus card is connected, the following parameters are displayed:
Figure 4-19
Modbus card settings
−
Comm. address
parameter
Set a communications address for the Modbus card over the dual in-line package
(DIP) switch on the Modbus card. The value cannot be changed on the LCD.
−
Baud rate
parameter
Set a baud rate for the Modbus card over the DIP switch on the Modbus card. The
value cannot be changed on the LCD.