UPS2000-G-3 kVA
User Manual (CTC)
4 Control Panel
Issue 02 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
39
−
Single/Parallel
parameter
The values include
Single
and
Parallel
. The default value is
Single
. The parameter
is configurable after the inverter shuts down.
−
Redundant UPSs
parameter
Set the number of redundant UPSs. The value ranges from 0 to 3. The default value
is 0. The parameter is configurable after the inverter shuts down.
Output
screen
Figure 4-22
Output screen
−
Voltage level
parameter
Set the system output voltage level. The values include 100 V (default), 110 V, and
120 V for single-phase output. Set it based on site requirements. The parameter is
configurable after the inverter shuts down.
−
Frequency level
parameter
Set the system output frequency level. The values include 50 Hz, 60 Hz (default),
and
Automatic
. If the value is
Automatic
, the power-on bypass frequency ranges
from 40 Hz to 55 Hz, and the system output frequency is 50 Hz; if the power-on
bypass frequency ranges from 55 Hz to 70 Hz (excluding 55 Hz), and the system
output frequency is 60 Hz. The parameter is configurable after the inverter shuts
down.
−
Volt. adj. coef.
parameter
You can adjust the inverter rated output voltage. The values include ±5%, ±4%,
±3%, ±2%, ±1%, and 0% (default). Press + or – to increase or decrease the output
voltage. The parameter is configurable after the inverter shuts down.
If you set
Converter mode
to
Enabled
, the UPS cannot transfer to bypass mode or
maintenance bypass mode. If you shut down the inverter, the loads power off.
−
Converter mode
parameter
Determine whether to enable inverter mode. The values include
Disabled
and
Enabled
. The default value is
Disabled
. In converter mode, the output voltage and
frequency are fixed at the specified values. The parameter is configurable after the
inverter shuts down.
Bypass
screen