UPS2000-G-3 kVA
User Manual (CTC)
A Alarm Handling
Issue 02 (2019-05-05)
Copyright © Huawei Technologies Co., Ltd.
74
Alarm
ID
(Alarm
ID-Alar
m
Cause)
Alarm
Name
Alarm
Level
Alarm
Clear
Mode
Impact on the System
Repair Proposal
0060-02
Inverter
fault
Critical
Power-off
clear
The UPS shuts down.
The UPS may transfer to
another working mode or
shut down.
Possible cause: The
inverter relay is faulty.
Measure: Contact Huawei
technical support for repair.
0060-03
Inverter
fault
Critical
Power-off
clear
0060-04
Inverter
fault
Critical
Power-off
clear
Possible cause: The
inverter output is
short-circuited.
Measure: Rectify output
port short circuits. After
you clear the alarm, restart
the UPS. If the alarm
persists, contact Huawei
technical support for repair.
0060-05
Inverter
fault
Critical
Automatic
clear
Possible causes:
The mains experiences
instantaneous
high-voltage impact.
The output has special
loads such as sensitive
loads and rectification
loads.
The output has
transformer loads but
the transformer mode is
not set.
The hardware is faulty.
Measures:
After you rectify the
fault, restart the UPS.
Check whether the load
type is supported by the
UPS.
Enable the transformer
mode.
Contact Huawei
technical support for
repair.
0060-07
Inverter
fault
Critical
Automatic
clear
The UPS starts upon
shutdown.
The UPS may transfer to
another working mode or
Possible causes:
The ambient
temperature exceeds
40º
C.