UPS2000-G-(1 kVA-3 kVA)
User Manual
4 Setting Control Panel
Issue 08 (2017-08-04)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
40
Alar
m ID
Alar
m
Cause
ID
Alar
m
Name
Alarm
Severity
Alarm Clear
Mode
Trigger
Condition
Impact on
the System
Repair Proposal
the UPS
fails to
start.
If battery
packs are
connecte
d during
the
running
of the
UPS, the
UPS
transfers
to bypass
mode.
Measure:
Connect to the
mains in
non-battery test
state.
Minor
This alarm is
automatically
cleared.
For standrd
model, the
voltage of
each battery
is lower than
11.28 V. For
long backup
time model,
the voltage of
each battery
is lower than
10.9 V.
The power
supply from
the UPS is
not affected.
29
1
Batter
y
requiri
ng
mainte
nance
Minor
This alarm is
automatically
cleared.
The battery
voltage is
lower than
the battery
replacement
voltage (11
V) when
batteries are
in self-check
mode.
The power
supply from
the UPS is
not affected.
Possible cause:
The actual
number of
batteries does
not meet
requirements.
Measure: Check
that the actual
number of
batteries meets
requirements.
Possible cause:
The battery is
damaged.
Measure:
Contact the
dealer or
Huawei
technical
support to
Minor
This alarm is
automatically
cleared.
The voltage
of each
battery is
lower than 5
V, or is
higher than
15 V (when
the UPS is
not started).
The UPS
remains in
the current
state and
cannot start.