UPS2000-G-(1 kVA-3 kVA)
User Manual
9 Specifications
Issue 08 (2017-08-04)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
67
Item
1 kVA
2 kVA
3 kVA
Charg
er
rated
charge
current
Standard
model
1 A
Long
backup
time
model
4 A
Float
chargi
ng
voltag
e
Standard
model
27.3 V DC±1%
54.7 V DC±1%
82.1 V DC±1%
Long
backup
time
model
41.0 V DC±1%
82.1 V DC±1%
109.4 V DC±1%
Equali
zed
chargi
ng
voltag
e
Standard
model
28.3 V DC±1%
56.6 V DC±1%
84.9 V DC±1%
Long
backup
time
model
42.5 V DC±1%
84.9 V DC±1%
113.3 V DC±1%
Table 9-7
Power backup specifications of the battery pack
Battery
Pack
Load
UPS2000-G-1KR
TL (min)
UPS2000-G-2KR
TL (min)
UPS2000-G-3KR
TL (min)
1 Battery
group
100%
15.0
6.5
7.0
75%
21.0
10.0
11.0
50%
39.0
18.0
17.0
25%
77.0
37.0
45.0
2 Battery
groups
100%
36.0
17.0
16.0
75%
47.0
25.0
25.0
50%
83.0
45.0
45.0
25%
159.0
85.0
85.0
3 Battery
groups
N/A
N/A
39.0
27.0
N/A
N/A
55.0
40.0
N/A
N/A
95.0
70.0
N/A
N/A
175.0
130.0
4 Battery
groups
N/A
N/A
63.0
39.0
N/A
N/A
87.0
55.0