UPS2000-G-(1 kVA-3 kVA)
User Manual
4 Setting Control Panel
Issue 08 (2017-08-04)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
31
Display
Setting
Press ▼ or ▲ to adjust and set the highest
input voltage in bypass mode.
230
–
264:
The value range is 230 V AC to
264 V AC, and the default value is 264 V
AC.
The highest input voltage in bypass mode should be higher than the highest input voltage in ECO mode.
Set the lowest input voltage in bypass mode.
Display
Setting
Press ▼ or ▲ to adjust and set the lowest
input voltage in bypass mode.
170
–
220:
The value range is 170 V AC to
220 V AC, and the default value is 170 V
AC.
The lowest input voltage in bypass mode should be lower than the lowest input voltage in ECO mode.
Set the battery capacity.
Display
Setting
Press ▼ or ▲ to adjust and set the UPS
battery capacity.
18
–
999:
Set the UPS battery capacity in the
range of 18 Ah to 999 Ah. (The default
value for standard model is 9 Ah and not
configurable. The default value for long
backup time model is 18 Ah.)
Set the discharge time limit.
Display
Setting