UPS2000-G-(1 kVA-3 kVA)
User Manual
9 Specifications
Issue 08 (2017-08-04)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
65
Item
1 kVA
2 kVA
3 kVA
Rated output voltage
200 V AC/208 V AC/220 V AC/230 V AC/240 V
AC
Output voltage tolerance
±1%
Output frequency range
In normal mode, the UPS output frequency is
consistent with the input frequency, which is 50
Hz or 60 Hz with the tolerance of ±3 Hz.
In battery mode, the frequency is 50 Hz or 60 Hz
(tolerance ±0.05%).
Total distortion of output voltage
waveform (THDv)
< 6% (non-resistive load)
< 3% (resistive load)
Crest factor
A maximum of 3:1
Inverter overload capability
When the ambient temperature is 0–35°C:
−
105%–110%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 10 minutes.
−
110%–130%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 1 minutes.
−
130%–150%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 3 seconds.
−
> 150%: The UPS automatically shuts down
(in battery mode) or transfers to bypass mode
(in line mode) after 0.5 seconds max.
When the ambient temperature is 35–40°C:
−
105%–110%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 5 minutes.
−
110%–130%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 30 seconds.
−
130%–150%: The UPS automatically shuts
down (in battery mode) or transfers to bypass
mode (in line mode) after 1.5 seconds.
−
> 150%: The UPS automatically shuts down
(in battery mode) or transfers to bypass mode
(in line mode) after 0.5 seconds max.
Dynamic voltage tolerance ±5%
±5%
Average frequency tracking rate
1 Hz/s
Transfer time
Transferring
from normal
mode to battery
mode
0