Parameter
Description
Value Range
Overfrequency derating
Enables or disables the
overfrequency derating
function.
Disable
Enable
Freq for triggering OF
derating (Hz)
For a specific grid code, the
SUN2000 output active
power needs to be derated
when the grid frequency
exceeds the set value.
When the output
frequency is 50 Hz, the
value range is
45.00–55.00 Hz.
When the output
frequency is 60 Hz, the
value range is
55.00–65.00 Hz.
Freq for exiting OF derating
(Hz)
Specifies the frequency
threshold for exiting
overfrequency derating.
When the output
frequency is 50 Hz, the
value range is
45.00–55.00 Hz.
When the output
frequency is 60 Hz, the
value range is
55.00–65.00 Hz.
Cutoff frequency of
overfrequency
Specifies the frequency
threshold for cutting off
overfrequency derating.
When the output
frequency is 50 Hz, the
value range is
45.00–55.00 Hz.
When the output
frequency is 60 Hz, the
value range is
55.00–65.00 Hz.
Cutoff power of
overfrequency
Specifies the power
threshold for cutting off
overfrequency derating.
[0, 100]
Recovery grad of OF
derating (%/min)
Specifies the power
recovery gradient for
overfrequency derating.
[5, 20]
7.4.5.5 Time Setting
To set time, choose
Grid-connect config
>
Expert
>
Time setting
from the
Operation
console