Parameter
Description
Value Range
Comm interruption duration
(min)
Specifies the duration for
determining communication
interruption. Used for
automatic shutdown for
protection in case of
communication interruption.
[1, 120]
Soft start time (s)
Specifies the duration for
the power to gradually
increase when the SUN2000
starts.
[20, 1800]
AFCI
The North American
standard requires the
SUN2000 to provide the DC
arc detection function.
Disable
Enable
AFCI detection adaptive
mode
Adjusts the sensitivity of arc
detection.
High
Moderate
Low
OFF due to abnormal
grounding
This function is used to
detect whether the
SUN2000 is properly
grounded before starting the
SUN2000, or to detect
whether the ground cable is
disconnected when the
SUN2000 is working. This
parameter is set to
Enable
by default. For certain types
of power grids, if an
isolation transformer
connects to the output side
of the SUN2000, you need
to set
OFF due to
abnormal grounding
to
Disable
after checking that
the SUN2000 is properly
grounded. Then the
SUN2000 can start
normally.
If you are not sure whether
the SUN2000 connects to
such a power grid, check
with your supplier or
Huawei technical support.
Disable
Enable
Emergency stop switch DI
Specifies the I/O signal of
the emergency stop switch.
Disable
NC
NO