8.3 SUN2000 Troubleshooting
Alarm severity levels are defined as follows:
Major: The SUN2000 enters Shutdown mode and disconnects from the power grid to
stop generating power after a fault occurs.
Minor: Some components are faulty but the SUN2000 can still connect to the power grid
and generate power.
Warning: The SUN2000 output power decreases due to external factors.
The reset alarm cannot be automatically cleared after the fault is rectified. Choose
Device info
>
Alarm management
>
Active alarm
on the FusionHome app, as shown in
Figure 8-13
, to manually
clear it or power off the SUN2000. Powering off the SUN2000 to clear the alarm: Turn off the AC
output switch and then the DC input switch. After 5 minutes, turn on the AC output switch and then
the DC input switch.
Contact your installer if the fault still persists after completing all failure analysis procedures listed
above.