SUN2000-(5KTL, 6KTL)-M0
User Manual
C Setting Export Limitation Parameters
Issue 03 (2019-07-19)
Copyright © Huawei Technologies Co., Ltd.
80
Table C-1
Setting export limitation parameters
Parameter
Value Range
Description
Control mode
Not restricted
Grid connected with zero
power
Power-limited grid
connected
If this parameter is set to
Not restricted
, the
SUN2000 output power
is not limited. The
SUN2000 can export its
rated power to the power
grid.
If this parameter is set to
Grid connection with
zero power
and the
SUN2000 is connected
to a power meter, the
output power of the
SUN2000 is supplied
only to the local load,
but not the power grid.
If this parameter is set to
Power-limited grid
connection
and the
SUN2000 is connected
to a Smart power sensor,
the SUN2000 supplies
power limited based on
the setting of
Grid-tied
Point Power
to the
power grid.
Closed-loop controller
External controller
Inverter
Set this parameter to
External controller
when the
SmartLogger1000A is
connected.
If multiple inverters are
cascaded, set this
parameter to
External
controller
.
If a single inverter is
used, set this parameter
to
Inverter
.
----End
Scenario 2: Multiple Inv SmartLogger1000A
See the