F IPS Test (for Italy CEI0-21 Grid Code only)
Issue 03 (2019-07-19)
Copyright © Huawei Technologies Co., Ltd.
84
F
IPS Test (for Italy CEI0-21 Grid Code
only)
Prerequisites
You have logged in to the app as
installer
. The initial password is
00000a
. Use the initial
password upon first power-on and change it immediately after login. To ensure account
security, change the password periodically and keep the new password in mind. Not changing
the initial password may cause password disclosure. A password left unchanged for a long
period of time may be stolen or cracked. If a password is lost, devices cannot be accessed. In
these cases, the user is liable for any loss caused to the PV plant.
Context
The Italy CEI0-21 grid code requires an IPS test for the SUN2000. During the IPS test
process, the SUN2000 consecutively tests the protection thresholds and time for 10-min
overvoltage, level 1 overvoltage, level 1 undervoltage, level 1 overfrequency, and level 1
underfrequency. The SUN2000 shuts down after the IPS test starts, and it restarts after the IPS
test is successful.
Procedure
Step 1
On the
Home
screen, choose
Device maintenance
>
IPS test
to access the IPS test screen.