SUN2000-(5KTL, 6KTL)-M0
User Manual
7 Maintenance
Issue 03 (2019-07-19)
Copyright © Huawei Technologies Co., Ltd.
63
Alarm ID Alarm
Name
Alarm
Severity
Possible Cause
Troubleshooting Suggestion
2035
Unbalance
d Grid
Voltage
Major
Cause ID = 1
The difference between grid
phase voltages exceeds the
upper threshold.
1.
If the alarm occurs occasionally,
the power grid may be abnormal
temporarily. The SUN2000
automatically recovers after
detecting that the power grid
becomes normal.
2.
If the alarm occurs frequently,
check whether the grid voltage is
within the acceptable range. If
no, contact the local power
operator.
3.
If the fault persists for a long
time, check the connection
between the AC switch and the
output power cable.
2036
Grid
Overfrequ
ency
Major
Cause ID = 1
Power grid exception: The
actual power grid frequency is
higher than the standard
requirement for the local
power grid.
1.
If the alarm occurs occasionally,
the power grid may be abnormal
temporarily. The SUN2000
automatically recovers after
detecting that the power grid
becomes normal.
2.
If the alarm occurs frequently,
check whether the grid
frequency is within the
acceptable range. If no, contact
the local power operator. If yes,
log in to the mobile phone app,
SmartLogger, or NMS to modify
the grid overfrequency
protection threshold with the
consent of the local power
operator.
2037
Grid
Underfreq
uency
Major
Cause ID = 1
Power grid exception: The
actual power grid frequency is
lower than the standard
requirement for the local
power grid.
1.
If the alarm occurs occasionally,
the power grid may be abnormal
temporarily. The SUN2000
automatically recovers after
detecting that the power grid
becomes normal.
2.
If the alarm occurs frequently,
check whether the grid
frequency is within the
acceptable range. If no, contact
the local power operator. If yes,
log in to the mobile phone app,
SmartLogger, or NMS to modify
the grid underfrequency
protection threshold with the
consent of the local power
operator.