SmartLogger1000
User Manual
7 WebUI
Issue 12 (2019-01-15)
Copyright © Huawei Technologies Co., Ltd.
209
No
.
Paramet
er Name
Function
Paramet
er Value
Description
7
Maximum
DC
voltage
Specifies the
PV-PE voltage
when
Operation
Mode
is set to
Normal
or
Commissioning
.
500–1500
V
If the PV module type is P, the parameter value indicates
the highest DC voltage between PV+ and PE. If the PV
module type is N, the parameter value indicates the
highest DC voltage between PV– and PE.
8
Maximum
output
voltage
Specifies the
highest output
voltage of the
PID module when
Operation Mode
is set to
Normal
or
Commissioning
.
0–500 V
If the offset mode is
PV/PE
, the parameter value indicates
the highest DC output voltage between PV and PE. If the
offset mode is
N/PE
, the parameter value indicates the
highest DC output voltage between N and PE.
9
IMD
access
Specifies whether
the PID module
and insulation
monitor device
(IMD) can
operate in cycle
mode.
Enable
Select
Enable
if you allow the PID module and IMD
operate in cycle mode.
Only the IMDs of mainstream suppliers such as DOLD
and BENDER are supported,and the IMDs must have
enabled dry contacts.
NOTICE
Only when
IMD access
is set to
Enable
, can you set
Periodic
PID runtime
,
Periodic IMD runtime
, and
IMD control dry
contact
.
Disable
Select
Disable
if you forbid the access of IMDs.
10
Periodic
PID
runtime
Specifies the
operating time
segment of the
PID module when
the PID module
and IMD operate
in cycle mode.
60–480
minutes
The IMD is shut down when the PID module is operating.
11
Periodic
IMD
runtime
Specifies the
operating time
segment of the
IMD when the
PID module and
IMD operate in
cycle mode.
15–480
minutes
The PID module is standby when the IMD is operating.
12
IMD
control
dry
contact
Dry contact No.
over which the
SmartLogger
controls the IMD
DO1,
DO2, and
DO3
PID01: Set appropriate ports based on the cable
connections between the IMD and the SmartLogger.