9 Maintenance
Issue 12 (2019-01-15)
Copyright © Huawei Technologies Co., Ltd.
274
No.
Symptom
Possible Cause
Measures
8
Emails
cannot be
received.
1.
The SmartLogger cannot communicate
with the email server.
2.
Ethernet parameters are not properly
set.
3.
Email parameters are not properly set.
1.
Connect the Ethernet network port of
the SmartLogger to the PC or router.
2.
Check that the Ethernet parameters are
correctly set.
3.
Check that the Email parameters are
correctly set.
9.3 Alarms
This topic describes the common faults in the SmartLogger and the troubleshooting measures.
describes the common faults and the troubleshooting measures.
Table 9-2
Alarms
Alarm
ID
Alarm
Alarm
Severity
Alarm
Sub-ID
Causes
Measure
1100
Abnorm
al
P-Contro
l
Major
1
Under the active
power
AI
remote control
mode, the
feedback
command data
of the AO port
cannot be read
due to the
ADAM fault,
power
disconnection,
or abnormal
link.
1.
Check whether the cable connections to
the DI ports are correct.
2.
Enter the active power
Dry contact
remote control
configuration page and
check the mapping table of the current
DI signal configuration. Contact the
power grid company to check the
completeness of the combination
configurations in the mapping table and
check whether the configurations
comply with the requirements of the
power grid company.
1101
Abnorm
al
Q-Contr
ol
Major
1
Under the
reactive power
Dry contact
remote control
mode, the four
DI ports read
commands
beyond the
configuration.
1.
Check whether the cable connections to
the DI ports are correct.
2.
Enter the reactive power
Dry contact
remote control
configuration page and
check the mapping table of the current
DI signal configuration. Contact the
power grid company to check the
completeness of the combination
configurations in the mapping table and
check whether the configurations
comply with the requirements of the
power grid company.