SmartLogger1000
User Manual
7 WebUI
Issue 12 (2019-01-15)
Copyright © Huawei Technologies Co., Ltd.
175
No.
Parameter
Description
Unit
Value Range Remarks
9
Communicati
on interrupt
shutdown
The standards of certain
countries and regions require
that the inverter must shut down
after the communication is
interrupted for a certain time.
N/A
Disable
Enable
If
Communication
interrupt shutdown
is set to
Enable
and
the inverter
communication has
been interrupted for a
specified time (set by
Communication
interruption
duration
), the
inverter will
automatically shut
down.
10
Communicati
on
interruption
duration
Specifies the duration for
determining communication
interruption, and is used for
automatic shutdown for
protection in case of
communication interruption.
min
[1, 120]
N/A
11
Communicati
on resumed
startup
If this parameter is enabled, the
inverter automatically starts
after communication recovers.
If this parameter is disabled, the
inverter needs to be started
manually after communication
recovers.
N/A
Disable
Enable
For the 600 V
inverter, this
parameter is displayed
when
Communication
interrupt shutdown
is set to
Enable
.
12
Soft start
time
Specifies the duration for the
power to gradually increase
when the inverter starts.
s
[20, 1800]
This parameter is set
to
360
by default if
the Australian
AS4777 grid code is
selected, to
300
by
default if the Italian
CEI0-21 or CEI0-16
grid code is selected,
and to
600
by default
if the Egyptian
EGYPT grid code is
selected.
13
AFCI
The North American standard
requires the inverter to provide
the DC arc detection function.
N/A
Disable
Enable
This parameter is
supported by only the
products marked
-US
.
Arc detection
adaptation mode
and
AFCI self-test
are
displayed only when
AFCI
is set to
Enable
.
14
Arc detection
adaptation
mode
Adjusts the sensitivity of arc
detection.
N/A
High
Moderate
Low
15
AFCI
self-test
Send the AFCI self-test
command manually.
N/A
N/A