No.
Parameter Description
Unit
Value Range
Remarks
68
Step
injection
module
Refers to a control
module that injects step
reactive power to
promote frequency offset
when the offset deviation
of grid voltage and
frequency is very small.
When islanding occurs,
the inverter and load
reaches balance.
N/A
Disable
Enable
N/A
69
Frequency
feedback
module K1
value
Specifies level-1 gain of
the frequency feedback
module.
N/A
[0, 100]
N/A
70
Frequency
feedback
module K2
value
Specifies level-2 gain of
the frequency feedback
module.
N/A
[0, 100]
N/A
71
Restart
mode after
grid failure
Specifies how the
inverter restarts after a
grid fault is rectified.
N/A
Manual
Automatic
N/A
72
Restart
duration
after grid
failure
Specifies the delay
before restart after a grid
fault is rectified.
s
6s, 150s, 180s, 240s, and
300s
N/A
73
System soft
start time
Specifies the duration for
the power to gradually
increase when the
inverter starts.
s
[20, 800]
N/A
74
Voltage rise
suppression
The Japanese standard
requires that the inverter
should control the active
power and reactive
power when the output
voltage exceeds a certain
value to ensure the grid
voltage stability.
N/A
Disable
Enable
N/A
75
Voltage rise
suppression
reactive
adjustment
point
The Japanese standard
requires that the inverter
should adjust the reactive
power to prevent the grid
voltage from rising when
the output voltage
exceeds a certain value.
V
107.0 V, 107.5 V, 108.0
V, 108.5 V, 109.0 V,
109.5 V, 110.0 V, 110.5
V, 111.0 V, 111.5 V,
112.0 V, and 112.5 V
N/A