7 WebUI
Issue 12 (2019-01-15)
Copyright © Huawei Technologies Co., Ltd.
181
Grid Parameters
Table 7-6
Parameter description
No.
Parameter
Description
Unit
Value Range
Remarks
1
Grid code
Set this parameter based
on the grid code of the
country or region where
the inverter is used and the
inverter application
scenario.
N/A
N/A
N/A
2
Output mode
Specifies whether the
inverter has an output
neutral wire based on the
inverter application
scenario.
N/A
Three-phase
three-wire
Three-phase
four-wire
This parameter is
supported by the
SUN2000-33KTL,
SUN2000-33KTL-A,
SUN2000-36KTL,
SUN2000-50KTL-M0,
SUN2000-60KTL-M0,
and the inverters named
with
-US
.
3
PQ mode
If
PQ mode 1
is selected,
the maximum AC output
power equals the
maximum apparent power.
If
PQ mode 2
is selected,
the maximum AC output
power equals the rated
output power.
N/A
SUN2000-36K
TL: PQ mode
1 (Pmax = 40
kW), PQ mode
2 (Pmax = 36
kW)
SUN2000-42K
TL: PQ mode 1
(Pmax = 47
kW), PQ mode
2 (Pmax = 42
kW)
SUN2000-50K
TL-M0,
SUN2000-60K
TL-M0: PQ
mode 1, PQ
mode 2
This parameter is
supported by the
SUN2000-36KTL,
SUN2000-42KTL,
SUN2000-50KTL-M0,
and
SUN2000-60KTL-M0.
4
Auto start
upon grid
recovery
Specifies whether to allow
the inverter to
automatically start after
the power grid recovers.
N/A
Disable
Enable
N/A
5
Grid
connection
duration after
power grid
recovery
Specifies the waiting time
for inverter restart after the
power grid recovers.
s
[0, 900]
This parameter can be
set to [150, 900] for the
1000 V and 1100 V
inverters under the
Japanese grid codes.