SmartACU2000B smart array controller
User Manual (with PID modules, 800 V AC)
2 Overview
Issue 05 (2019-01-20)
Copyright © Huawei Technologies Co., Ltd.
15
Part No.
Name
Specifications
Quantit
y
Label
10
PE bar
N/A
1
N/A
11
SmartLogger
SmartLogger2000-10-C
1
SmartLogger
(SL)
12
Fiber adapter
2LC/PC-2LC/PC-4
2
OFA01:
TX1 RX1
OFA02:
TX2 RX2
13
Position for the POE
SPD
N/A
1
N/A
14
Position for the POE
module
N/A
1
POE
15
ATB
N/A
1
ATB
16
Single-phase input
switch
32 A/2 P
1
QF01
17
Three-phase input switch
2 (left figure: knife fuse
switch)
25 A/3 P
1
FU02
Three-phase input switch
2 (right figure: circuit
breaker)
32 A/3 P
NOTE
The three-phase input switch 2 of some
specific models is a circuit breaker.
1
QF04
18
Three-phase input switch
1 (left figure: knife fuse
switch)
25 A/3 P
1
FU01
Three-phase input switch
1 (right figure: circuit
breaker)
32 A/3 P
NOTE
The three-phase input switch 1 of some
specific models is a circuit breaker.
1
QF02
19
24 V DC input and
output terminals
6 P/supporting 0.2–10 mm
2
(or 24–8
AWG) cable connection
NOTE
The 24 V DC output terminal can be
used to connect to the EMI with a
maximum load of 30 W.
1
JX02
20
RS485 communications
terminal
12 P/supporting 1–2.5 mm
2
(or
18–14 AWG) cable connection
1
JX01
21
PID02
SmartPID2000
1
PID02
22
PID01
SmartPID2000
1
PID01