14
Table 2-4
Components and reserved installation positions
Part No.
Name
Specifications
Quantit
y
Label
1
Functional earthing bar
N/A
1
FE01
(PID01
functional
earthing
bar)
FE02
(PID02
functional
earthing
bar)
2
24 V DC power module
(left figure)
AC input: 100–240 V, 50 Hz/60
Hz
DC output: 12 V DC, 60 W
(maximum); 24 V DC, 30 W
(Maximum)
NOTE
If an external 24–28 V DC input is used,
the DC output voltage ranges from 21.5
V to 25.2 V.
1
U01
Power adapter (right
figure)
AC input: 100–240 V, 50 Hz/60
Hz
DC output: 12 V/2 A
3
PID01 input switch
AC: 3 A/3 P
1
QF03
4
PID02 input switch
AC: 3 A/3 P
1
QF05
5
Single-phase SPD
Uc = 385 V AC
30 kA/60 kA, 8/20 μs
4 P
NOTE
The single-phase SPD on the specific
model of smart array controller has three
poles.
1
F03
6
Three-phase SPD 1
Uc = 680 V AC
20 kA/40 kA, 8/20 μs
1 P
4
F01
7
Three-phase SPD 2
Uc = 680 V AC
20 kA/40 kA, 8/20 μs
1 P
4
F02
8
Position for the LAN
switch
N/A
1
SWITCH
9
PLC CCO
PLC CCO01A
1
PLC CCO