SmartACU2000B smart array controller
User Manual (with PID modules, 800 V AC)
2 Overview
Issue 05 (2019-01-20)
Copyright © Huawei Technologies Co., Ltd.
25
Components listed in the table need to be installed onsite.
Select either an MCCB or a knife fuse switch as the three-phase power switch. If you
select an MCCB, ensure that the let-through energy of the MCCB meets requirements. The
breaking capacity depends on the limited short-circuit current on the low voltage side of
the transformer.
Models of the components inside the box-type transformer are specified by the box-type
transformer vendor.
Table 2-7
Cables to be prepared in the fiber ring network scenario
No.
Cable
Cable Name/Specifications
Cross-sectional
Area Range of the
Cable
(Recommended)
Source of
Cable
1
Three-phase
AC power
cable
Four-core (L1, L2, L3, and functional
earthing) outdoor copper armored cable
with three OT-M6 terminals (L1, L2, and
L3) and one OT-M4 terminal (functional
earthing)
When the rated AC voltage on the
low-voltage side of the box-type
transformer is less than or equal to 500 V,
the operating voltage between the
three-phase AC power cable and the
ground should be greater than or equal to
600 V.
When the rated AC voltage on the
low-voltage side of the box-type
transformer is greater than 500 V and less
than or equal to 800 V, the operating
voltage between the three-phase AC
power cable and the ground should be
greater than or equal to 1000 V.
8–10 mm
2
(10
mm
2
)
8 AWG
Prepared
by the
customer
2
Peripheral
network cable
CAT 5E outdoor shielded network cable with
an outer diameter less than 9 mm (0.35 in.)
and internal resistance not greater than 1.5
ohms/10 m (1.5 ohms/32.81 ft), as well as a
shielded RJ45 connector
N/A
Prepared
by the
customer
3
Peripheral
RS485
communication
s cable
A computer cable (DJYP2VP2-22 2x2x1) or
armored shielded twisted pair that can be
used outdoors and OT-M4 terminals
0.5–1 mm
2
(1
mm
2
)
20–18 AWG (18
AWG)
Prepared
by the
customer
4
Cabinet PE
cable
Outdoor copper cable with an OT-M6
terminal
6–16 mm
2
(16
mm
2
)
10–6 AWG (6
AWG)
Prepared
by the
customer