PDU8000 Modular Precision PDC V2.0
User Manual
5 Installation Guide
Issue 03 (2018-01-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
46
Figure 5-17
Not tied at bends
Figure 5-18
Extra length for easy plug and unplug
Figure 5-19
Stroking cables
Cable Layout
Table 5-6
Cable layout rules
No.
Cable Layout Rule
1
The armoring layers of armored cables are grounded.
2
The PDC ground cable is secured to the equipment room ground bar. The
resistance between the PDC ground cable and the equipment room ground
bar is less than 0.1 ohm.
3
Cables are securely connected in the correct phase sequence.