PDU8000 Modular Precision PDC V2.0
User Manual
7 MDU Commissioning Guide
Issue 03 (2018-01-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
97
System overvoltage (%)
Specifies the upper alarm threshold in relative to the rated voltage. The value ranges from
105
to
125
.
Overvoltage ack.time (s)
Specifies the duration for confirming an overvoltage alarm. The value ranges from
1
to
10
.
System undervoltage (%)
Specifies the lower alarm threshold in relative to the rated voltage. The value ranges from
75
to
95
.
Undervoltage ack.time (s)
Specifies the duration for confirming an undervoltage alarm. The value ranges from
1
to
10
.
Overload (%)
Specifies the overload alarm threshold in relative to the rated load. The value ranges from
100
to
120
.
Overload ack.time (s)
Specifies the duration for confirming an overload alarm. The value ranges from
1
to
10
.
Overfrequency (Hz)
Specifies the overfrequency alarm threshold in relative to the rated frequency. The value
ranges from
1
to
10
.
Overfrequency ack.time (s)
Specifies the duration for confirming an overfrequency alarm. The value ranges from
1
to
10
.
Upper load cur. thre. (%)
Specifies the upper alarm threshold in relative to the rated current. The value ranges from
80
to
100
.
Lower Load cur. thre. (%)
Specifies the lower alarm threshold in relative to the rated current. The value ranges from
30
to
80
.
7.4.3.6 Setting Wizard
On the
Settings
screen, tap
Setting Wizard
to access the screen.