Item
Specifications
Output circuit
breakers
Single- or three-phase 16 A/20 A/32 A/40 A/63 A; maximum: 144
single-phase routes or 48 three-phase routes
Surge protection
Class C SPD in standard configuration
Cabling
400 A/250 A/160 A input scenario: Cables can be routed in and
out from the top or bottom.
630 A input scenario: Cables can be routed in from the top and
out from the top or bottom.
Environmental
friendliness
RoHS, REACH
Overvoltage level
II
Operating
temperature
–5°C to +40°C
Relative humidity
5%–95%, non-condensing
Altitude
≤ 2000 m (If the altitude exceeds 2000 m, the device is derated
according to GB/T3859.2-93.)
Table 3-3
Safety and EMC
Item
Specifications
Safety
CCC, CE, TL
N/A
EMC
Conducted emission (CE)
EN55022 CLASS A
Radiated emission (RE)
EN55022 CLASS A
Voltage fluctuation and flicker
EN61000-3-3
EN61000-3-11
Harmonic current
EN61000-3-2
EN61000-3-12
Conducted susceptibility (CS)
IEC61000-4-6
Radiated susceptibility (RS)
IEC61000-4-3
Electrostatic discharge (ESD)
IEC61000-4-2
Electrical fast transient (EFT)
IEC61000-4-4
Surge
IEC61000-4-5
Voltage dip and short
interruption
IEC61000-4-11 2004