PDU8000 Modular Precision PDC V2.0
User Manual
7 MDU Commissioning Guide
Issue 03 (2018-01-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
105
Figure 7-51
Upgrade Software (5)
The MDU is not restarted if the software for the monitoring board is activated and is restarted if the
software for the MDU is activated.
If the PDC is powered off when the software for the monitoring board is being upgraded, the
information about the monitoring board is not displayed after the MDU is restarted. In this case, tap
Upgrade Software
to continue the upgrading process. If the PDC is powered off when the software
for the MDU is being upgraded, perform the upgrading again after the MDU is restarted.
After the software is upgraded, the MDU parameters remain unchanged and do not need to be reset.
----End
7.4.4.2 Loading Configurations
Context
The
Load Config.
function enables you to set system parameters.
Note that the function may change the original model configuration parameter values.
Exercise caution when using this function.
Procedure
Step 1
Connect a USB flash drive to the
USB Host
port.