PDU8000 Modular Precision PDC V2.0
User Manual
5 Installation Guide
Issue 03 (2018-01-25)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
45
Figure 5-15
Cable ties in the same direction
Figure 5-16
Binding cables in different colors
Table 5-4
Cable bundle binding interval
Cable Bundle Diameter (mm)
Binding Interval (mm)
< 10
150
10-30
200
> 30
300
Cable Bending
Table 5-5
Cable bending rules
No.
Cable Bending Rule
1
Cables are not overly bent as over bending may damage the cable cores.
2
Unless otherwise stipulated, the bending radius should be 10 times greater
than the cable diameter if the installation space is sufficient.
3
Cables are not tied where they bend, as shown in
4
Cables must be a little longer than the exact cable route length to facilitate
plug and unplug, as shown in
5
Cables should be neatly and loosely arranged to eliminate abnormal stress
on certain cables, as shown in