Terminating a PGND Cable with an OT Terminal
Strip the PGND cable.
A: OT terminal
B: PGND cable
C: exposed cable conductor
L1: length of the exposed cable
When you are skillful, you can determine L1
based on the length of the OT terminal lug.
When striping off the insulation layer of the
PGND cable, take care not to damage or nick the
metal conductor of the cable.
Fit the exposed cable into the OT terminal.
Ensure that the cable conductor does not
protrude more than 2 mm from the OT terminal.
Crimp the OT terminal lug.
The impression left from crimping the lug may
differ depending on the crimping tool used.
Mapping between the cross-sectional area of a
cable conductor (C) and the length of an exposed
cable (L1)
Cross-sectional
Area of C (mm
2
)
L1 (mm)
1
1.5
2.5
4
7
7
7
8
Crimp the OT
terminal lug.
Terminating an Indoor PI Power Cable with an EPC4 Connector
Components of an EPC4 connector (EPC is the
abbreviation for easy power connector.)
Strip off the sheath of conductors.
8 mm
Use a screwdriver to push the sliding blocks until
the in-position mark is completely exposed.
Insert conductors.
(+)
(-)
Black
Blue
Push back the sliding blocks until
they are in position. Then, check
whether the conductors are secure
by gently pulling them. If the
conductors slide outward or the
wires of the conductors are
exposed outside the holes, remove
the conductors, cut the split wires,
and then strip and install the
conductors again.
(1) EPC4 connector
(2) Scale
(3) Sliding block
(4) Holes for conductors
A conductor must be in the center of a hole.
Wrong:
The conductor is deviated from the
center of the hole.
Wrong:
The conductor is not perpendicular
to the hole.