NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
3 Installation Guide
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
55
Port
Pin
Signal attribute
Description
CN16
Pin1
RTU-RS485-D+
Monitoring
communications
Pin2
RTU-RS485-D-
Pin3
GND1
Pin4
Null
/
Pin5
Null
/
Pin6
GND2
Teamwork
communications
Pin7
GROUP-RS485-D+
Pin8
GROUP-RS485-D-
CN17
Pin1
RTU-RS485-D+
Monitoring
communications
Pin2
RTU-RS485-D-
Pin3
GND1
Pin4
Null
/
Pin5
Null
/
Pin6
GND2
Teamwork
communications
Pin7
GROUP-RS485-D+
Pin8
GROUP-RS485-D-
The cables must be shielded cables, and the shielding layer must be reliably grounded.
Connecting Teamwork Cables
NetCol8000-A013 supports teamwork networking (hand-in-hand). In networking, a maximum
of 32 smart cooling products can be teamworked. After power-on, choose
Setting
>
User
Menu
>
Teamwork Setting
, and set
Enable Teamwork Resistor
for the controllers of the
first and last smart cooling products to
Yes
.
Smart cooling products in a teamwork group must be of the same model.