NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
E Controller Menu
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
168
Menu
Name
Default
Value
Settings Range
Air Filter RT out Alarm
4320h
2160h to 6480h
Smoke Sensor Alarm
Enable
Enable/Disable
Floor Water Alarm
Enable
Enable/Disable
Fire Alarm
Enable
Enable/Disable
Setting
>
Admin Menu
>
Alarm
Setting
>
Electric Heater
Run Time out Alarm
Enable
Enable/Disable
Run Time out Thres
30000
20000h to 40000h
Setting
>
Admin Menu
>
Alarm
Setting
>
Wet Film Humidifier
Humid RT out Alarm
Enable
Enable/Disable
Humid RT out Thres
8760h
4380h to 17520h
Pump RT out Alarm
Enable
Enable/Disable
Pump RT out Thres
40000h
10000h to 50000h
Setting
>
Admin Menu
>
Alarm
Setting
>
Delete All Historical
Alarms
Delete All Historical Alarms
No
Yes/No
Setting
>
Admin Menu
>
System Setting
>
System
Control
Forced Cooling
Enable
Enable/Disable
Dehumidifying
Enable
Enable/Disable
Humidifying
Enable
Enable/Disable
Heating
Enable
Enable/Disable
Freq Rise Temp Demand
50%
0% to 100%
Freq Drop Temp Demand
–50%
–100% to 0%
Heating Temp Demand
–100%
–100% to 0%
Dehumtemp Comp
Enable
Enable/Disable
Dehum Comp On Demand
0%
–50 to +50%
Dehum Comp Off Demand
50%
0 to 100%
Setting
>
Admin Menu
>
System Setting
>
Temp&Humid
Sensor
Max Temp Set
32.0
18°C to 35°C
Min Temp Set
18.0
18°C to 35°C
Max Humid Set
90.0%RH
20.0%RH to 100.0%RH
Min Humid Set
30.0%RH
20.0%RH to 70.0%RH
Temp P-band
3.0°C
0.5°C to 20.0°C
Temp Deadzone
1.0°C
0.1°C to 20.0°C
Dehum P-band
5.0%
1.0% to 90.0%
Dehum Dead zone
1.0%
0.5% to 90.0%