NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
5 System Operation and Maintenance
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
104
Procedure
Step 1
Open the front door, and turn off the indoor unit circuit breaker and circuit breaker in the
power distribution cabinet.
Step 2
Use a Phillips screwdriver to remove the nine screws that secure the baffle plate of the electric
control box, and remove the baffle plate from the electric control box.
Figure 5-7
Removing the baffle plate from the electric control box
Step 3
Remove the cables from the main control board.
Take a photo before performing this step so that you know how to bind the cable ties and install the
cable terminals later.
Step 4
Remove the eight screws that secure the main control board, and remove the main control
board.
Step 5
Install the new main control board in reverse order.
Step 6
Tap
on the home screen, and tap
Yes
on the start confirmation screen displayed.
Ensure that the smart cooling product is running normally without any alarms.
----End
5.4.1.7 Replacing the Drive Board of the Indoor Fan
Prerequisites
The fan drive board needs to be replaced.