NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
5 System Operation and Maintenance
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
106
Step 6
Tap
on the home screen, and tap
Yes
on the start confirmation screen displayed.
Ensure that the smart cooling product is running normally without any alarms.
----End
5.4.1.8 Replacing the LCD
Prerequisites
The LCD needs to be replaced.
A spare LCD with the correct software version is available.
Choose
Maintenance
>
USB Wizard
>
One-Click Export
to export historical data to a
USB flash drive.
1.
The USB port of the USB flash drive must comply with the USB2.0 standard.
2.
The FAT32 USB flash drive (4, 8, 16, or 32 GB) should be used.
3.
The upgrade file must be stored in the root directory of the USB flash drive.
Context
Tool: Phillips screwdriver
Procedure
Step 1
Open the front door.
Step 2
Remove the cables from the LCD.
Step 3
Use a Phillips screwdriver to remove the four screws from the rear of the LCD.
Step 4
Remove the LCD and backplane.
Step 5
Install the new LCD and backplane in reverse order.
Step 6
Install the LCD cables.
Step 7
Choose
Maintenance
>
USB Wizard
>
Configuration Import
to import historical data.
Step 8
After the cables are reconnected, the home screen is displayed on the LCD. Check whether
the display is normal.
----End
5.4.1.9 Replacing an EEV
Prerequisites
An EEV and its coil need to be replaced.
A spare EEV and a coil of the same model are available and functional.